Therm-A-Seal is a new generation of intumescent fire
seal, designed for use in fire door assemblies which are required
to control the spread of fire through buildings. The PVC casings
contain an expandable graphite-based intumescent compound which
unlike some products, is unaffected by moisture in the air and
so does not require to be carefully protected when fitted. The
seals are rebated into the door's head and jambs.
Therm-A-Seal
is suitable for
FD20, FD30 and FD60 single and
double doorsets in timber, steel (or both).
Single action and double swing doorsets (latched or unlatched).
Therm-A-Seal is available in brown, white, cream,
red and a variety of wood grain effects.
Therm-A-Seal is supplied in standard lengths of 1050mm
and 2100mm (with or without double-sided self-adhesive tape on
the underside of the PVC casing). It is available in the following
nominal dimensions: 10 x 4mm, 15 x 4mm, 20 x 4mm, 25 x 4mm, 30
x 4mm and 38 x 4mm.
Therm-A-Seal has passed numerous tests carried out
in accordance with BS 476 : parts 20 & 22 (details available
on request).
| Typical
Applications |
Latched single-leaf, single-swing
30 minute (FD30) timber fire doors:
Single length of Therm-A-Seal 10 x 4mm down each jamb & across
the head. |
Un-latched single-leaf, single or double-swing
30 minute (FD30) timber fire doors:
Single length of Therm-A-Seal 10 x 4mm down each jamb & depending
on the door a wider section may be required across the head. |
Latched single-leaf, single-swing 60 minute
(FD60) timber fire doors:
Single length of Therm-A-Seal 20 x 4mm down each jamb & across
the head. Un-latched doors may require additional protection
across the head. |
|